关于485接口保护问题,如图那种更合适?TVS和自恢复保险的位置。
|
|||
niba
38
主题
131
回复 |
发表于2017-04-25 12:36:04
|
显示全部楼层
1#
电梯直达
图1图2
|
|||
fhongkai
1
主题
9
回复 |
发表于2017-05-06 23:16:38
|
显示全部楼层
13#
I think PTC Fuse cannot be used for sure if you need to let the RS-485 Port survive from Such continual-High Voltage shock instead of ESD/Low Voltage Shock,etc.I think for 220/380V Voltage Level,at least TVS-GDT-Fast-acting fuse for two-level Protection... PTC Fuses Acts tooooooooo Slow compared with Fast-acting Fuse,I think,according to the Datasheet of LittelFuse.. |
|